8.4 Technicaldata
MX²30S MX²35S MX²40S MX²55S MX²60S MX²80S MX²95S
Processair
Figuresquoted are rated, basedon a fan inlet
temperatureof20°Candanairdensityof1,2kg/m
3
.
Ratedairflow(m
3
/s) 0,750 0,972 1,111 1,528 1,667 2,222 2,639
Ratedairflow(m
3
/h) 2700 3500 4000 5500 6000 8000 9500
Minimumavailablestati
cpressure(Pa)
300 300 300 300 300 300 300
Fan motorpower (kW) 2,2 3,0 3,0 3,0 7,5 7,5 7,5
Reactivation air
Ratedairflow(m
3
/
s)
0,250 0,300 0,350 0,300 0,550 0,700 0,500
Ratedairflow(m
3
/h)
900 1080 1260 1080 1980 2520 1800
Minimumavail
ablestaticpressure(Pa)
300 300 300 300 300 300 300
Fanmotorpow
er(kW)
0,75 1,1 1,1 1,1 1,5 2,2 1,5
Ratedcurr
entwith
processan
dreactivation fan,Standard/EEP
Current
(Amps/Phase)at380V,50/60Hz(A)
7 101010192019
Curre
nt(Amps/Phase)at400V,50/60Hz (A)
7 9 9 9 18 19 18
Curr
ent(Amps/Phase)at 415V,50/60Hz (A)
7 9 9 9 17 18 17
Cur
rent(Amps/Phase)at440V,50/60Hz(A)
6 8 8 8 16 17 16
Ra
tedcurrentwith
p
rocessandreactivationfan,ERP
Current(Amps/Phase)at 380 V, 50/60Hz (A) 7 10 10 10 19 21 19
Current(Amps/Phase) at 400V, 50/60Hz (A) 7 9 9 9 18 20 18
Current(Amps/Phase) at 415V, 50/60Hz (A) 7 9 9 9 18 19 18
Current(Amps/Phase) at 440V, 50/60Hz (A) 6 9 9 9 17 18 17
Reactivation heater
Temperature increase across heater (°C) 100 100 100 100 100 100 100
Reactivationheaterpower (kW) 30 36 42 36 66 84 60
Reactivationheaterpower,ERP (kW) 25 36 36 36 60 78 60
Totalrequiredpower(50Hz)
With processand reactivationfans (kW) 3,4 4,6 4,6 4,6 9,5 10,2 9,5
Without process fan (kW) 1,2 1,6 1,6 1,6 2,0 2,7 2,0
58
Technicalspecification
190TEN–1089–G1412