Section 40 00-02-0994
2016-06-28 - 12 -
• *Prestart Delay 2 (crank through): (available in Auto Mode only) After an auto start condition
has been accepted by the controller, this delay begins timing, and the prestart output turns on.
When this delay expires, the output remains on, and the auto sequence continues. The output
turns off when the engine actually starts. During this delay, the controller checks for faults, J1939
com, etc.
• Crank: This is a timed state to try and start the engine.
• Crank Rest: This is a timed state to rest the starter between cranks in case the engine did not
start during the crank state.
• False Start Check: This is a non-timed state that will ensure the engine stays above the crank cut
RPM after cranking.
• Warm-up: (available in Auto mode only) This is a timed state that will allow the engine to
change from idle to desired warm-up RPM after starting. Warm-up will only set as low as the
minimum RPM set point.
• Line Fill 1: (available in Auto mode only) This is a timed state that will exit if the timer times out
or the pressure set point for this state is reached.
• Line Fill 2: (available in Auto mode only) This is a timed state that will exit if the timer times out
or the pressure set point for this state is reached.
• Running Loaded: This is a non-timed state that the controller will stay in until a stop condition
occurs.
• Cool-down: (available in Auto mode only) This is a timed state that will allow the engine to run
at a desired speed to cool down before allowing to go into a stopped state.
• Energize to Stop: This is a timed state that will control an output in order to stop the engine.
• Spindown: The time allotted for the engine to stop all revolutions and be in a stopped state with
no frequency.
• Post Crank Lockout Delay (setup): This delay begins timing when the engine actually starts.
During this delay, the selected function is ignored. When this delay expires, the selected function
is armed. During the duration of this delay, the selected function can cycle from active to not
active and not reset the delay.
• Post Warm-up Lockout Delay (setup): This delay begins timing when the warm-up delay expires.
During this delay, the selected function is ignored. When this delay expires, the selected function
is armed. During the duration of this delay, the selected function can cycle from active to not
active and not reset the delay.
• Bubble Lockout Delay (setup): This delay begins timing when the selected function is active. If the
selected function is removed during this delay, the delay resets to zero. If the selected function
remains active throughout this delay, the selected action will occur.