Section 40 00-02-0994
2016-06-28 - 33 -
Overspeed Shutdown: shuts down the engine when the speed reaches the set higher limit parameter for
speed.
Factory set to 2400 RPM.
Throttle Menu
Throttle Type: allows the selection of J1939 TSC1, Pulse Inc/Dec or Analog 0-5VDC as the throttle type for the
engine.
Factory set to J1939 TSC1.
J1939 TSC1: this setting will be used when an electronic engine is used for J1939 Throttling. (Verify with
Engine Dealer this type of throttling is accepted on the specific engine.)
Pulse Inc/Dec: this setting will be used when throttling a mechanical engine, using a throttle actuator and
also an electronic engine using digital pulses into the ECU for throttling.
Analog 0-5 VDC: this setting will be used for throttling an electronic engine utilizing 0-5V output.
Auto Throttle Type
: Factory set to NON PID Auto Throttle.
NON PID Auto Throttle: this type does not use the P I D adjustments found in the Transducer setups in the
Application menu.
PID Auto Throttle: this type does use the P I D adjustments found in the Transducer setups in the Application menu.
Press Target RPM Step Size: this is the step size of the target RPM when pressing and quickly releasing the
push button. The actual rate of change is much higher when throttling in auto vs. manually with the push buttons.
Factory set to 10 RPM per each press of the button.
Hold Target RPM Step Size: this is the step size of the target RPM when pressing and holding the push button. The actual
rate of change is much higher when throttling in auto vs. manually with the push buttons. Factory set to 50 RPM per each
press and hold of the button.
Throttle Deadband RPM: (only appears when Pulse Inc/Dec or Analog, 0-5 VDC is chosen for the Throttle
Type) format of # RPM. Plus/minus value added to the target to provide a range of RPM during which the throttle
is not active. No throttling will occur when the engine RPM is within the RPM deadband.
Throttle Inc/Dec Pulse: (only appears when Pulse Inc/Dec is chosen) format of # mS. The amount of time to
pulse the throttle. Increase this value for faster engine response, decrease this value for slower engine response.
Throttle Inc/Dec Pulse Delay: (only appears when Pulse Inc/Dec is chosen) format of # mS. The amount of
delay time before pulsing the throttle. Increase this value for slower engine response, decrease this value for
faster engine response.
Throttle Inc Rate
: the rate the engine is signaled to increase in RPM. Factory set to 200 RPM/s.
Throttle Dec Rate
: the rate the engine is signaled to decrease in RPM. Factory set to 200 RPM/s.
Analog Minimum Value: (only appears when analog throttle type is chosen) The analog throttle output will not
go lower than this set point. Factory set to .50 V.
Analog Maximum Value
: (only appears when analog throttle type is chosen) The analog throttle output will not
go higher than this set point. Factory set to 4.5 V.
Input / Output Menu
Digital Inputs (1-6): for each of the digital inputs, the ability to select the following parameters exists: