Murphy ML2000 - Advanced Engine Settings Glossary

Murphy ML2000
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Section 40 00-02-0994
2016-06-28 - 30 -
Low Battery Warning: allows the operator to select the desired warning in the controller for Low Battery
to alert the operator when the voltage of the battery is too low.
Factory set to 10.0 V.
Weak Battery Warning: allows the operator to select the desired warning in the controller for Weak
Battery to alert the operator when the battery is becoming too weak to function.
Factory set to 11.0 V.
Underspeed Shutdown: allows the operator to select the desired shutdown in the controller for
Underspeed Shutdown to alert the operator when the engine is being shut down due to operating below
the established minimum speed when in the running loaded state for this shutdown.
Factory set to 0 RPM.
Overspeed Shutdown: allows the operator to select the desired shutdown in the controller for Overspeed
Shutdown to alert the operator when the engine is being shut down due to operating above the
established maximum speed when in the running loaded state for this shutdown.
Factory set to 2400 RPM.
Advanced Engine Settings
J1939 Address Claim: allows the setting of the address for the controller used in the J1939 engine setting.
Factory set to 228.
ECU Source Address: source address of the ECU being connected to. Normally set to 0, 1 or 2.
Factory set to
0.
ECU Hour Select: choose from ECU Hours (engine hours reported by the ECU) or Internal (hours calculated
internally by the MPC-20 (provided the RPM>50).
Factory set to ECU Hours.
Crank Attempts: format of 0.00 to 20.00. The number of times the engine will attempt to start before providing
an overcrank shutdown.
Factory set to 3.
Crank Disconnect Speed: the speed at which the crank will disconnect barring other input parameters.
Factory
set to 500 RPM.
Clutch Engage Speed: the speed at which the clutch will engage.
Factory set to 1200 RPM.
Clutch Disengage Speed: the speed at which the clutch will disengage. Factory set to 1000 RPM.
Run to Destruct: choose from Enable or Disable. This setting will prevent the controller from shutting down the
engine for any fault shutdown to allow a run to destruct condition. This setting is primarily used for marine or fire
pump applications. CAUTION: If enabled, the operator must manually select Disable to allow shutdowns
and protect the engine.
Factory set to Disable.
Timers: establish parameters for the:
Auto Start Delay: the auto start condition must remain active throughout this delay for an auto start to
occur. If the auto start condition is removed during this delay, the delay is reset to zero.
Factory set to
00.00.03
Auto Stop Delay: this auto stop condition must remain active throughout this delay for an auto stop to
occur. If the auto stop condition is removed during this delay, the delay is reset to zero.
Factory set to
00.00.03
Minimum Run Time: auto stop conditions are ignored during this delay. Factory set to 00.00.00
ECU Stabilize Timer: on startups, this delay allows the ECU to stabilize and broadcast on the CAN bus
prior to actual cranking.
Factory set to 00.00.05