Section 40 00-02-0994
2016-06-28 - 31 -
Crank Time: length of time the crank output is turned on during cycle cranking. Factory set to 00.00.10
Crank Rest: length of time the crank output is turned off during cycle cranking.
Factory set to 00.00.10
Prestart Delay 1: after an auto start condition has been accepted by the controller, this delay begins
timing, and the prestart #1 output turns on. When this delay expires, the output is turned off, and the auto
sequence continues.
Factory set to 00.00.00
Prestart Delay 2: after an auto start condition has been accepted by the controller, this delay begins
timing, and the prestart #2 output turns on.
Factory set to 00.00.00
Prestart Delay 2 Mode: this setting determines if the prestart #2 output is active through the crank state
or only through the prestart #2 state. Prestart functions are available in Manual mode.
Factory set to
PreCrank.
Energize to Stop Time: this delay begins timing and an output is turned on after an auto stop condition
has been accepted by the controller. The output is turned off when this delay expires.
Factory set to
00.00.00
Spindown Timer: this delay begins timing when there is no call to run and the engine speed is zero. No
auto start functions will occur until this delay expires.
Factory set to 00.00.30
Post Crank Lockout Setup: this is a setup for a delay that begins timing when the engine actually starts.
During this delay, the selected functions (Warnings and Shutdowns) are ignored. When this delay
expires, the selected functions are armed. During the duration of this delay, the selected functions can
cycle from active to not active and not reset the delay.
Post Crank Lockout Time. Factory set to 00.00.30
Post Crank Lockout 1. Factory set to Low Oil Pressure
Post Crank Lockout 2. Factory set to Low Discharge Pressure
Post Crank Lockout 3. Factory set to Disabled
Post Crank Lockout 4. Factory set to Disabled
Post Crank Lockout 5. Factory set to Disabled
Post Warm-up Lockout Setup: this is a setup for a delay that begins timing when the warm-up delay
expires. During this delay, the selected functions (Warnings and Shutdowns) are ignored. When this
delay expires, the selected functions are armed. During the duration of this delay, the selected functions
can cycle from active to not active and not reset the delay.
Post Warm-up Lockout Time. Factory set to 00.00.00
Post Warm-up Lockout 1. Factory set to Disabled
Post Warm-up Lockout 2. Factory set to Disabled
Post Warm-up Lockout 3. Factory set to Disabled
Post Warm-up Lockout 4. Factory set to Disabled
Post Warm-up Lockout 5. Factory set to Disabled
Bubble Lockout Setup: this is a setup for a delay that begins timing when the selected functions are
active. If the selected functions are removed during this delay, the delay resets to zero. If the selected
functions remain active throughout this delay, the selected action for the parameter will occur.
Bubble Lockout Time. Factory set to 00.00.00
Bubble Lockout 1. Factory set to Disabled
Bubble Lockout 2. Factory set to Disabled
Bubble Lockout 3. Factory set to Disabled
Bubble Lockout 4. Factory set to Disabled
Bubble Lockout 5. Factory set to Disabled