Section 40 00-02-0994
2016-06-28 - 34 -
Digital input 1. Factory set to Disabled
Digital Input 2. Factory set to Auto Start Momentary/Maintained
Digital Input 3. Factory set to Auto Stop Momentary/Maintained
Digital Input 4. Factory set to Low Coolant Level
Digital Input 5. Factory set to Low Lube Oil Level
Digital Input 6. Factory set to Water in Fuel
Function:
Disabled
Single Contact Start/Stop
Auto Start Momentary / Maintained
Auto Stop Momentary / Maintained
Remote Alarm Acknowledge
Low Fuel Level
Fuel Leak
Fuel Filter Restriction
Low Lube Oil Level
Low Coolant Level
Remote Stop
Idle Engine
Water in Fuel
No Flow
Engine Overspeed
Crank Termination
Air Damper Closed
Air Filter Restriction
Battery Charger Fail
Oil Filter Restriction
Run To Destruct Override
User 1 through User 6
Speed 1 through Speed 5
Parking Brake
Neutral Switch
Active
B- (ground input to a function chosen above) Factory Default
B+ (battery positive to a function chosen above)
Open (sender/switch is open)
Action
Not Used
Warning
Shutdown Factory Default
Shutdown, Controlled (The input will initiate an auto stop. The input has to be inactive for the
controller to accept a new auto start signal.)
Relay Control: used to control one of the relay outputs
DI Speed Set points: used in place of Throttle Inc/Dec. Provides five throttle set points to which the engine will
throttle.
These speed inputs will override any other throttling type. When inputs are not active, any other throttling type in use
will resume. Digital input 1 will override 2 through 4. Digital 2 will override 3 through 5, and so on.
Analog Inputs (1-8): for each of the analog inputs, the ability to select the following parameters exists:
Analog input 1. Factory set to Start Control (not configurable)
Analog Input 2. Factory set to Disabled
Analog Input 3. Factory set to Disabled
Analog Input 4. Factory set to Disabled
Analog Input 5. Factory set to Disabled
Analog Input 6. Factory set to Disabled