Section 40 00-02-0994
2016-06-28 - 43 -
REGISTER #
TYPE
DESCRIPTION
40211
Read Only
J1939.Engine.Diesel Particulate Filter 1 Soot Load Percent.
40212
Read Only
J1939.Transmit.Diesel Particulate Filter Regeneration Inhibit Switch
40213
Read Only
J1939.Engine.Diesel Particulate Filter Active Regen Inhibited Due to Inhibit
Switch
#0
(LSB) Inhibited Due to Inhibit Switch: (1) yes (0) no
#1
Reserved
#2
Reserved
#3
Reserved
#4
Reserved
#5
Reserved
#6
Reserved
#7
Reserved
#8
Reserved
#9
Reserved
#10
Reserved
#11
Reserved
#12
Reserved
#13
Reserved
#14
Reserved
#15
(MSB) Reserved
40214
Read Only
State Timer.
40215
Read Only
Engine RPM Set Point.
40216
AllPurposeAutoStartFunction
#0
Single Contact
#1
Local Start Key
#2
Two Contact Maintained
#3
Two Contact Momentary
#4
Pressure Transducer
#5
Level Transducer
#6
Flow Transducer
40217
Read/Write
Pressure Deadband. kPa
40218
Read/Write
Level Deadband. Feet
40219
Read/Write
Flow Deadband. US Gal/min
40220
Read/Write
Start Temperature. Celsius
40221
Read/Write
Stop Temperature. Celsius
40222
Read Only
Current Ambient Temperature. Celsius
40223
Read/Write
Maintain Flow. US Gal/min
40224
Read/Write
RPM Low Idle
40225
Read Only
Service Reminder: Air Filter Life
40226
Read Only
Service Reminder: Air Filter Life Remaining
40227
Read Only
Service Reminder: Battery Life