Technical Data
User manual 59719_hdb_en_12 27 / 65
4.4.2 Environmental characteristics
Cable length ≤30 m
Input characteristic EN 61131-2 Type 1 + Type 3
Input filter 1 ... 10 ms, adjustable
Input (DI)
Output (DO)
Connection/female connector M12
Cable cross section ≤0.75 mm²
Cable length ≤30 m
Output current Per pin ≤2 A
Switching frequency Resistive load ≤25 Hz
Climatic
Operating temperature -25 °C ... +70 °C
Storage temperature -40 °C ... +85 °C
Installation height Above sea level ≤3000 m
Relative humidity ≤95 %
Mechanical
Vibration test EN 60068 Parts 2-6 5 ... 500 Hz;
const. amplitude 1 mm;
acceleration 15 g
Shock test EN 60068 Parts 2-27 50 g @ 11 ms
Electrical safety
Degree of protection IP68
Protection class III
Degree of pollution 2
Emitted EMC interference
Radio interference field strength EN 61000-6-4 Emission QP: 40 dBμ V/m
@ 30 ... 230 MHzQP: 47
dBμ V/m
@ 230 ... 1000 MHz
EMC immunity
Electrostatic
discharge (housing)
EN 61000-4-2 ±4 kV @ contact
±8 kV @ air
Electromagnetic high-frequency fields
(housing)
EN 61000-4-3 RF field 10 V/m
Rapid transient electric disturbances
(burst)
DC inputs/outputs
EN 61000-4-4 ±2 kV I/O supply
±1 kV data line/
±1 kV I/O line
Magnetic field EN 61000-4-8 30 A/m @ 50 Hz
Conducted interferences,
high-frequency fields
EN 61000-4-6, asymmetric 10 V

Table of Contents