Operation
User manual 59719_hdb_en_12 43 / 65
0x0011 VendorText R 64 www.murrelektronik.com.
0x0012 ProductName R 64 MVP12-P6 DIO16 8xM12A
IOLA12 B0
MVP12-P6 DIO16 8xM12A
IOLA12 E0
0x0013 ProductID R 64 59719 59819
0x0014 ProductText R 64 Digital I/O hub
MVP12-P60 - IO-Link Class
A
DIO16 8xM12A
Basic Firmware Edition:
2 bytes IN / 2 byte Out
Digital I/O hub
MVP12-P60 - IO-Link Class
A
DIO16 8xM12A
Extended Firmware Edition:
4 bytes IN / 2 byte Out
0x0015 SerialNumber R 16 Running serial number
set during production
0x0016 HardwareRevision R 64 e.g. “01.00”
0x0017 FirmwareRevision R 64 e.g. “V.1.00.00”
0x0018 ApplicationSpe-
cificTag
R 16 ... 32 User-specific designation
e.g. “System 3 / Port 4”
0x0019 FunctionTag R 32
0x001A LocationTag R 32
Diagnosis
0x0020 Error Count R 2
0x0024 DeviceStatus R 1 0: Device is operating properly
1: Maintenance Required
2: Out of Specification
3: Functional Check
4: Failure
5 ... 255: Reserved
0x0025 DetailedDeviceSta-
tus
R variable 6 x (octet 1: EventQualifier,
octet 2, 3: EventCode)
0x0028 ProcessDataInput R PD
length
0x0029 ProcessDataOutput R PD
length
0x0031
...
0x003F
Reserved for pro-
files
ISDU
index
DPP
index
Object name Access Length
in bytes
Meaning / default value