6-18 Wiring Safety Devices
Magnum 4A Control Wiring and Adjustment Manual www.NabcoEntrances.com
Part #C-00084 Rev. 9-09-16
Turn OFF Power.
arrow points to the Exterior
.
DN 0644
EXT
INTERIOR SIDEEXTERIOR SIDE
Figure 6-5
Please see .
.
Figure 6-6 Panic Latch (Fail Safe)
DN 0570
BROWN
BLACK
RED
WHITE
VIOLET
ORANGE
23456 12356
To Magnum Control
Safety with Lockout
during door swing
To Terminal #5
Normally Closed Contacts
Continuous Safety
Normally Closed Contacts
Red
Red
Part # 11- 0941
Panic Latch Kit
TERMINAL BLOCK
#1 BROWN
#2 ORANGE
#3 VIOLET
#4 WHITE
#5 RED
#6 BLACK
24VAC NEUTRAL
24VAC HOT
CONTINUOUS SAFETY
SAFETY WITH LOCKOUT
ACTIVATION
When using normally closed safety, all panic breakout devices connected to
continuous safety must be wired in series. If sensor contacts
or a panic latch opens, the door can not activate.
BROWN
BLACK
RED
WHITE
VIOLET
ORANGE
23456 1234
To Magnum Control
Safety with Lockout
To Terminal #5
Normally Closed Contacts
Continuous Safety
Normally Closed Contacts
Red
Red
RedRed
SIMULTANEOUS PAIRS
SINGLE DOORS
Panic Latch must be positioned so that
arrow marked "EXT" points to exterior of building.
(Contacts must open when door is broken out)
Panic Latch must be positioned so that
arrow marked “EXT” points to exterior of building.
(Contacts must open when door is broken out)
Safety with Lockout
(Overhead Sensors)
Normally Closed Contacts
On double egress doors
using two overhead safety
sensors with normally closed
safety, outputs of both
sensors must be wired in
series.
(Overhead Sensor)( Door Mounted Sensor)
Continuous Safety
Normally Closed Contacts
(Door Mounted Sensor)
To Terminals
4 and 5
COMMON