Chapter 4 Feature Set Description
FP-2000/2010/2015 User Manual 4-4 ni.com
Commands sent to a missing module return an error response, but the
FP-20xx stores the commands and applies the effects of these commands
if a suitable replacement module is inserted.
When a new I/O module is connected in place of one that was removed, the
FP-20xx first verifies that the replacement I/O module is compatible with
the one that was removed. If the I/O module is the same as, or is compatible
with, the one removed, the FP-20xx configures the replacement I/O module
with its predecessors configuration and output value settings.
Table 4-1 shows how modules are configured after HotPnP replacement.
LED Indicators
The FP-20xx has several LEDs to convey status information.
POWER LED
The green POWER LED is lit while the FP-20xx is powered up. This LED
indicates that the power supply connected to the FP-20xx is acceptable, and
that the FP-20xx is supplying power to the I/O modules.
STATUS LED
The red STATUS LED is off in normal operation mode. The FP-20xx
indicates specific error conditions by flashing STATUS aspecificnumber
of times. Refer to the STATUS LED Error Indications section of
Table 4-1. Module Configuration Results after HotPnP Replacement
Replacement
Module
Start in Factory
Default
Replacement Module
Configuration after HotPnP
Compatible with the removed
module
Either Enabled or
Disabled
Same as the configuration of the
removed module
Incompatible with the removed
module but compatible with the
stored Snapshot information
Disabled Same as the configuration stored in
the Snapshot
Enabled Factory default configuration of
replacement module
Incompatible with the removed
module and incompatible with the
stored Snapshot information
Either Enabled or
Disabled
Factory default configuration of
replacement module

Table of Contents