Appendix C Troubleshooting
FP-2000/2010/2015 User Manual C-4 ni.com
Runaway Start-Up Application
If a runaway startup application causes the FP-20xx to become
unresponsive, you must power down the FP-20xx, then reboot it with either
the DISABLE VI switch or SAFE MODE switch in the ON position.
Restarting the module with the DISABLE VI switch ON prevents any VIs
from running at startup. Restarting it with the SAFE MODE switch ON
starts the FP-20xx in safe mode, and the embedded LabVIEW RT engine is
not launched. Refer to the DIP Switches section of Chapter 4, Feature Set
Description, for more information about these DIP switches.
STATUS LED Error Indications
The FP-20xx indicates specific error conditions by flashing the red
STATUS LED a specific number of times. The following table describes
the STATUS LED flashing sequences and the corresponding error
condition.
Table C-1. STATUS LED Flashes and Corresponding Error Conditions
Number
of Flashes
Error Condition
0 (stays lit) The FP-20xx did not power on correctly. Contact
National Instruments for assistance.
1 The FP-20xx is in reset mode or is unconfigured.
Refer to Appendix B, Resetting the FP-20xx, formore
information about reset mode. Refer to Chapter 3,
Hardware and Software Configuration,formore
information about configuration.
2 The FP-20xx has detected an error in its firmware. This
usually occurs when an attempt to upgrade the firmware
is interrupted. Repeat the firmware upgrade process.
3 The FP-20xx is in safe mode. Download the software as
described in Appendix D, Installing LabVIEW RT
Software.
4 (or more) The FP-20xx has detected an unrecoverable error.
Contact National Instruments for assistance.