EasyManuals Logo

Nederman FlexPAK 800 Installation And Service Manual

Nederman FlexPAK 800
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
FlexPAK 800/1000
25
EN
7 Troubleshoong
For informaon on fuses, see Secon ‘3.4 Fuses’ and the included electrical diagrams.
There is no over current relay. The frequency converter parameter for maximum current is
adjusted from the factory and is not to be adjusted.
If a fault occurs which cannot be adjusted according to the following descripons, a
Nederman service technician is to be called.
7.1 Tools
To carry out troubleshoong, it is necessary to have a mulmeter with V DC and ohm
measuring capabilies.
7.2 Remove the lid of the start and control unit
Remove the lid as follows:
1. Unscrew the four plascs screws in the corner of the control cabinet.
2. Li of the lid.
3. Idenfy the PLC and the terminals in the boom of the cabinet.
Table 7-1: Trouble shoong guide
Error Possible cause Soluon
The unit
unexpectedly goes
directly into Running
mode when the
Standby/Running
buon is pressed.
• A valve at a workstaon is open
and its micro switch is acvated
• The PS cable is damaged with
its wires short-circuited
If the PS cable is damaged, press the Standby/Running
buon to put the unit into O mode and invesgate the
fault. If necessary, loosen the PS cable from the control
unit, see the electrical diagrams, and use an ohmmeter
across the leads in turn to locate the fault.
Defect PT100
temperature sensor.
Check whether the PT100 sensor is defecve as follows:
1. Disconnect the PT100 sensor wire from terminal 77 and
measure the resistance between terminal 78 and the
disconnected sensor wire.
2. Measure the resistance in the sensor using an
ohmmeter. The values in the table below are standard
values, so a deviaon from the measured value is
normal. If the averaged output (in ohm) deviates more
than ±2% from these values, the sensor will need to be
replaced.
Temperature (°C) Averaged output (ohm)
0 100
20 110
80 131
135 150
If the sensor has a resistance >150 ohm, there will be a
high temperature alarm. To check whether the sensor
input is working correctly, disconnect the PT100 wire at
terminal 77 and connect a jumper between terminals 77
and 78. Press the OK buon on the PLC to reset the alert.
If the alert disappears, the PT100 sensor input is working,
and the PT100 the sensor will need to be replaced.

Other manuals for Nederman FlexPAK 800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nederman FlexPAK 800 and is the answer not in the manual?

Nederman FlexPAK 800 Specifications

General IconGeneral
BrandNederman
ModelFlexPAK 800
CategoryDust Collector
LanguageEnglish

Related product manuals