Indoor units included in the multisplit system must be
configured correctly to be able to communicate with
outdoor units over different channels (indoor unitA, in-
door unitB, etc.).
The address for each indoor unit must correspond to the
connection between the indoor unit and outdoor unit's
cooling circuit; if the indoor unit is connected to the
cooling circuitA the address must also be A.
There are three different ways to address the indoor
units.
■
Addressing via DIP switch
The address is assigned via the DIP switches that are
on the indoor unit circuit board.
■
Addressing via remote control
Addressing is via the indoor unit remote control.
■
Automatic addressing
Each indoor unit is automatically assigned its own ad-
dress.
If several indoor units are connected to an outdoor unit,
the indoor units must be given an address that corres-
ponds to the connection used in the outdoor unit. This
is done either using the remote control or by adjusting
the indoor unit DIP switches.
Addressing via remote control
When addressing using remote control it is possible to connect up to eight indoor units to one outdoor unit.
Set the remote control according to the table below, direct it towards the desired indoor unit and keep the buttons
"FAN" and "iFEEL" pressed for more than five seconds. If the unit has received the command, four beeps are sounded
as confirmation. When you have heard the peeps, the unit starts to work with the new address.
Indoor unitButton
HGFEDCBA
AUTO
Operating mode ( or )
18 °C17 °C16 °C15 °C14 C13 °C12 °C11 °CSet point temperature
( / )
AUTO
Air deflector ( )
ON
TiO
2
air cleaner( )
OFF
Night program ( )
OFF
High power ( )
AG-WL10Chapter 7 | Addressing the indoor unit18
7 Addressing the indoor unit