Addressing via DIP switches
When addressing using DIP switches it is possible to connect up to four indoor units to one outdoor unit. See the
section "Positioning DIP switches" on the page 14 and set SW2 according to what is indicated in the table.
Indoor unit
DCBA
Automatic addressing
Caution
Before activating automatic addressing, check
that the indoor unit DIP switch for addressing
is factory set, in "OFF" mode.
Activating automatic addressing
Activate the climate installation and check that only error
code E0 (address missing) is visible on the indoor unit.
Start one of the indoor unit remote controls and set it
according to the table below.
SettingButton
AUTO
Operating mode ( or )
24 °CSet point temperature ( / )
AUTO
Air deflector ( )
ON
TiO
2
air cleaner( )
OFF
Night program ( )
OFF
High power ( )
Hold the ”FAN” and iFEEL buttons down for longer
than seven seconds and release them with the remote
control directed at one of the indoor unit receivers.
Ensure that the signal is only received by one of the
indoor units.
If the signal is received, the indoor module beeps five
times.
After a few seconds, the LED lamps display the follow-
ing combination to confirm that automatic addressing
is activated:
STANDBYTIMEROPERATION
Not litFlashesLit
NOTE
During the addressing process the IR receiver is
deactivated and the indoor units cannot receive
commands from the remote controls.
With automatic addressing activated, each indoor unit
is assigned its own address. During the addressing pro-
cess the system compressor and fans are running. Ad-
dressing takes 4-5 minutes per cooling circuit in the
outdoor unit.
The outdoor unit stops when all circuits have been
checked and the addresses assigned. The indoor units
go to standby mode and the IR receivers are activated,
regardless of whether the addressing functioned or not.
If the indoor units do not display any error codes, the
installation is ready for use. If the error code ”E0” (ad-
dress missing) is displayed on any of the indoor units you
can either try to address automatically again, or address
via the DIP switches or remote control.