COMMISSIONING WITHOUT HEAT PUMP
The indoor module can be used without a heat pump,
i.e only as an electric boiler, to produce heat and hot
water before the heat pump is installed, for example.
Connect the pipe for docking in from the heat pump
(XL8) with the pipe out to the heat pump (XL9).
Enter menu 5.2.2 System settings and deactivate the
heat pump.
NOTE
Select operating mode auto or manual when
the indoor module is to be used with the heat
pump again.
PUMP SPEED
The circulation pump (GP1) in VVM 320 is frequency
controlled and sets itself using control and based on
heating demand.
LEK
Available pressure circulation pump, GP1
0
10
2
0
20%
100%
30
40
50
60
70
80
0 200 400 600 800 1000 1200 1400
Tillgängligt tryck
(kPa)
Vattenflöde
(l/h)
Flow
(l/h)
Pressure
(kPa)
POST-ADJUSTMENT, VENTING
Initially, air is released from the hot water and venting
may be necessary. If gurgling sounds can be heard from
the climate system, the entire system will require addi-
tional venting. The installation is vented via vent valves
(QM20), (QM22) and other climate systems through
their relevant vent valves. When venting, VVM 320 must
be off.
41Chapter 6 | Commissioning and adjustingNIBE VVM 320

Other manuals for Nibe VVM 320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe VVM 320 and is the answer not in the manual?

Nibe VVM 320 Specifications

General IconGeneral
Dimensions (HxWxD)1800 x 600 x 615 mm
Power Supply230 V
Frequency50 Hz
Protection classIP21
Compatible withNibe heat pumps
DisplayTouch display
Smart Home IntegrationYes, via NIBE Uplink
Operating temperature0°C to +45°C
Relative humidityMax. 95 %
TypeControl unit for heat pumps

Related product manuals