MENU 5.11 - HEAT PUMP SETTINGS
Settings for installed heat pump can be made in the
submenus.
MENU 5.11.1 - EB101
Make settings specifically for the installed heat pump
and heating medium pump here.
MENU 5.11.1.1 - HEAT PUMP
Make settings for the installed heat pump here. To see
what settings you can make, see installation manual for
the heat pump.
MENU 5.11.1.2 - HEATING MEDIUM PUMP
(GP1)
op. mode
Setting range: auto / intermittent
Default value: auto
Set the operating mode of the heating medium pump
here.
auto: The heating medium pump runs according to the
current operating mode for VVM 320.
intermittent: The heating medium pump starts and stops
20 seconds before, and after, the compressor in the
heat pump.
speed during operation
heating, hot water, pool, cooling
Setting range: auto / manual
Default value: auto
Manual setting
Setting range: 1–100 %
Default values: 70 %
speed in wait mode
Setting range: 1–100 %
Default values: 30 %
max. allowed speed
Setting range: 80–100 %
Default values: 100 %
speed in prio. add. heat
Setting range: 1–100 %
Default values: 70 %
Set the speed at which the heating medium pump is to
operate in the present operating mode. Select "auto" if
the speed of the heating medium pump is to be regu-
lated automatically (factory setting) for optimal operation.
If "auto" is activated for heating operation, you can also
make the setting "max. allowed speed" which restricts
the heating medium pump and does not allow it to run
at a higher speed than the set value.
For manual operation of the heating medium pump de-
activate "auto" for the current operating mode and set
the value to between 1 and 100 % (the previously set
value for "max. allowed speed" no longer applies).
wait mode means heating or cooling operating mode
for the heating medium pump, when the heat pump
requires neither compressor operation nor electric addi-
tional heat and slows down.
61Chapter 8 | Control - MenusNIBE VVM 320

Other manuals for Nibe VVM 320

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nibe VVM 320 and is the answer not in the manual?

Nibe VVM 320 Specifications

General IconGeneral
Dimensions (HxWxD)1800 x 600 x 615 mm
Power Supply230 V
Frequency50 Hz
Protection classIP21
Compatible withNibe heat pumps
DisplayTouch display
Smart Home IntegrationYes, via NIBE Uplink
Operating temperature0°C to +45°C
Relative humidityMax. 95 %
TypeControl unit for heat pumps