Here you can set the charge pump speed for F135. You
can also choose to charge hot water with F135 at the
same time as the outdoor section produces cooling.
NOTE
The cooling accessory ACS 310 is required to
enable activation of ”hot water during cool-
ing”.
Caution
Cooling must be permitted in Menu 5.11.1.1
- heat pump so that ”hot water during cooling”
can be activated.
Menu 5.3.18 - outdoor air mixing (accessory
required)
Here you select which pump to use in the system.
Menu 5.3.19 - outdoor air mixing (accessory
required)
Here you select which pump to use in the system.
Menu 5.4 - soft in/outputs
Here you can select which in/output on the input circuit
board (AA3) the external contact function (page 27)
is to be connected to.
Selectable inputs on terminal block AUX1-5 (AA3-X6:9-
18) and output AA3-X7 (on the input circuit board).
Menu 5.5 - factory setting service
All settings can be reset (including settings available
to the user) to default values here.
NOTE
When resetting, the start guide is displayed
the next time the indoor module is restarted.
Menu 5.6 - forced control
You can force control the different components in the
indoor module and any connected accessories here.
NOTE
Forced control is only intended to be used for
troubleshooting purposes. Using the function
in any other way may cause damage to the
components in your climate system.
Menu 5.7 - start guide
When the indoor module is started for the first time
the start guide starts automatically. Start it manually
here.
See page 32 for more information about the start
guide.
See page 32 for more information about the start
guide.
Menu 5.8 - quick start
It is possible to start the compressor from here.
Caution
There must be a heating or hot water demand
to start the compressor.
Caution
Do not quick start the compressor too many
times over a short period of time as this may
damage the compressor and its surrounding
equipment.
Menu 5.9 - floor drying function
length of period 1 - 3, 5-7
Setting range: 0 - 30 days
Default value: 2 days
temp. period 1 - 3, 5-7
Setting range: 15 - 70 °C
Default value:
20 °Ctemp. period 1
30 °Ctemp. period 2
40 °Ctemp. period 3
40 °Ctemp. period 5
30 °Ctemp. period 6
20 °Ctemp. period 7
length of period 4
Setting range: 0 - 30 days
Default value: 3 days
temp. period 4
Setting range: 15 - 70 °C
Default value: 45 °C
Set the function for under floor drying here.
You can set up to seven period times with different
calculated flow temperatures. If less than seven periods
are to be used, set the remaining period times to 0
days.
Mark the active window to activate the underfloor
drying function. A counter at the bottom shows the
number of days the function has been active.
NOTE
During under floor drying, the heating medi-
um pump in 100% runs, regardless of the set-
ting in menu 5.1.10.
TIP
If operating mode "add. heat only" is to be
used, select it in menu 4.2.