44 Unidrive M/HS Frame 5 to 6 Power Installation Guide
Issue Number: 9
Figure 3-23 External EMC filter (size 5 to 6)
Table 3-8 Size 5 external EMC filter dimensions
Table 3-9 Size 6 external EMC filter dimensions
3.11.3 EMC filter torque settings
Table 3-10 Optional external EMC Filter terminal data
V: Ground stud
X: Threaded holes for footprint
mounting of the drive
Y: Footprint mounting hole diameter
Z: Bookcase mounting slot diameter. CS: Cable size
CT part
number
ABCDEHWV/XY/ZCS
4200-0312
395 mm
(15.55 in)
425 mm
(16.73 in)
106 mm
(4.17 in)
60 mm
(2.36 in)
33 mm
(1.30 in)
437 mm
(17.2 in)
143 mm
(5.63 in)
M6
6.5 mm
(0.26 in)
10 mm
2
(8 AWG)
4200-0402
4200-0122
2.5 mm
2
(14 AWG)
CT part
number
ABCDEHWV/XY/ZCS
4200-2300
392 mm
(15.43 in)
420 mm
(16.54 in)
180 mm
(7.09 in)
60 mm
(2.36 in)
33 mm
(1.30 in)
434 mm
(17.09 in)
210 mm
(8.27 in)
M6
6.5 mm
(0.26 in)
16 mm
2
(6 AWG)
4200-4800
4200-3690
CT part
number
Power
connections
Ground
connections
Max cable
size
Max torque Ground stud size Max torque
4200-0122
6 mm
2
(8 AWG)
1.8 N m (1.4 lb ft) M6 5.0 N m (3.7 lb ft)
4200-0312
6 mm
2
(8 AWG)
1.8 N m (1.4 lb ft) M6 5.0 N m (3.7 lb ft)
4200-0402
6 mm
2
(8 AWG)
1.8 N m (1.4 lb ft) M6 5.0 N m (3.7 lb ft)
4200-2300
16 mm
2
(6 AWG)
2.3 N m (1.70 Ib ft) M6 5.0 N m (3.7 lb ft)
4200-4800
16 mm
2
(6 AWG)
2.3 N m (1.70 Ib ft) M6 5.0 N m (3.7 lb ft)
4200-3690
16 mm
2
(6 AWG)
2.3 N m (1.70 Ib ft) M6 5.0 N m (3.7 lb ft)
Y
ED
Z
L
1
'
L
2
'
L
3
'
X
X
Y
V
Y
A
B
H
CW
Z
Z
CS
U1
V1 W1
Netz / Line
Last/Load
PE
U2
V2 W2