82 Unidrive M/HS Frame 5 to 6 Power Installation Guide
Issue Number: 9
5 Technical data
5.1 Drive technical data
5.1.1 Power and current ratings
For a full explanation of ‘Normal Duty’ and ‘Heavy Duty’ refer to the Control User Guide.
The continuous current ratings given are for maximum 40 C (104 F), 1000 m altitude and 3 kHz
switching frequency. Derating is required for higher switching frequencies, ambient temperature >40
C (104 F) and high altitude. For further information, refer to Chapter 5.1.2 Power and current
ratings (Derating for switching frequency and temperature) on page 84.
Table 5-1 200 V drive ratings (200 V to 240 V ±10 %)
Table 5-2 400 V drive ratings (380 V to 480 V ±10 %)
Model
Normal Duty Heavy Duty
Max
cont
output
current
Nominal
power
at 230 V
Motor
power
at 230 V
Peak
current
Max
cont
output
current
Open
loop
peak
current
RFC
peak
current
Nominal
power
at 230 V
Motor
power
at 230 V
AkWhpAAAAkWhp
05200250 30 7.5 10 33 25 37.5 50 5.5 7.5
06200330 50 11 15 55 33 49.5 66 7.5 10
06200440 58 15 20 63.8 44 66 88 11 15
Model
Normal Duty Heavy Duty
Max
cont
output
current
Nominal
power
at 400 V
Motor
power
at 460 V
Peak
current
Max
cont
output
current
Open
loop
peak
current
RFC
peak
current
Nominal
power
at 400 V
Motor
power
at 460 V
AkWhpAAAAkWhp
05400270 30.0 15.0 20.0 33.0 27.0 40.5
54.0
11.0 20.0
05400300 31.0 15.0 20.0 34.1 30.0 45.0
60.0
15.0 20.0
06400350 38.0 18.5 25.0 41.8 35.0 52.5
70.0
15.0 25.0
06400420 48.0 22.0 30.0 52.8 42.0 63.0
84.0
18.5 30.0
06400470 63.0 30.0 40.0 69.3 47.0 70.5
94.0
22.0 30.0