2.4.3 ID300 Ratings
Note: The mains current value is a typical value which depends on the source impedance. The higher
the impedance, the lower the current.
Note: The mains current value is a typical value which depends on the source impedance. The higher
the impedance, the lower the current.
Supply ID300 Drive Motor
Voltage Max Input Current
Size ID300K
Output Power
(V) (A) kW HP
230V
1ph / 3ph
8.1 1 12030 0.75 1.0
9.1
2
22035 0.9 1.25
12 22052 1.1 1.5
14.3 22057 1.5 2.0
230V
3ph
10.2
3
32075 1.8 2.4
12.2 32078 2.2 3.0
12.2 32120 3.0 4.0
14.8 32155 4.0 5.0
Supply ID300 Drive Motor
Voltage Max Input Current
Size ID300K
Output Power
(V) (A) kW HP
400V
3ph
3.4
1
14021 0.75 1.0
3.5 14025 0.9 1.25
3.5 14030 1.1 1.5
3.9 14033 1.5 2.0
7
2
24042 1.8 2.4
7.5 24050 2.2 3.0
8 24070 3.0 4.0
9.5 24085 4.0 5.0
13
3
34119 5.5 7.5
16 34155 7.5 10.0