www.usmotors.com32
ID300/302 Integrated Motor Drive | Connections
41
Relay Contacts
42
Default Function
Drive OK indicator (Closed when power applied and drive OK)
Contact Voltage Rating
240 Vac, Installation over-voltage category II
Contact Maximum Current Rating
2 A AC 240 V
4 A DC 30 V resistive load Current limit and trip
Contact Minimum Recommended Rating 12 V 100 mA
Contact Type Normally open
Update Rate 1 ms
4.6.2SafeTorqueO󰀨Inputs(ID302Only)
TheSafeTorqueO󰀨functionprovidesameansforpreventingthedrivefromgeneratingtorquein
the motor with a very high level of integrity. It is suitable for incorporation into a safety system for a
machine.
ThesafetyfunctionisactivewhenoneorbothSTOinputsareinthelogic-lowstate,asspeciedinthe
controlterminalspecication.ThefunctionisdenedaccordingtoEN/IEC61800-5-2.
The design of safety-related control systems must only be performed by personnel with the
requiredtrainingandexperience.TheSafeTorqueO󰀨functionwillonlyensurethesafetyofa
machine if it is correctly incorporated into a complete safety system. The system must be subject
toariskassessmenttoconrmthattheresidualriskofanunsafeeventisatanacceptablelevel
for the application.
SafeTorqueO󰀨inhibitstheoperationofthedrive.SafeTorqueO󰀨DOES NOT provide electrical
isolation. The supply to the drive must be disconnected by an approved isolation device before
gaining access to power connections.
It is essential to observe the maximum permitted voltage of 5 V for a safe low (disabled) state of
SafeTorqueO󰀨.Theconnectionstothedrivemustbearrangedsothatvoltagedropsinthe0V
wiring cannot exceed this value under any loading condition. It is strongly recommended that the
SafeTorqueO󰀨circuitsbeprovidedwithadedicated0Vconductorswhichshouldbeconnected
to Terminals 32 and 33 at the drive.
There is no ID302 available for 230V supply.
For more details on STO inputs,
refer to http://www.leroy-somer.com/documentation_pdf/5512_en.pdf
CAUTION
!
WARNING
!