22 Unidrive M200 / M201 Control User Guide
Issue Number: 2
14 Digital Input 5
Terminal 14 default function Analog INPUT 1 / INPUT 2 select
Type
Positive logic only digital input. Frequency
input or motor thermistor input (bias for
DIN44081 ptc, KTY84, PT1000, PT2000
and other types) mode can be selected.
Voltage range 0 V to +24 V
Absolute maximum applied
voltage range
-18 V to +30 V relative to 0 V
Impedance 6.8 k
Input threshold 10 V ±0.8 V (IEC 61131-2)
Sample rate
1 ms when routed to destinations Pr 06.035
or Pr 06.036, otherwise 4 ms.
41
Relay contacts
42
Default function Drive OK indicator
Contact voltage rating 240 Vac, Installation over-voltage category II
Contact maximum current rating
2 A AC 240 V
4 A DC 30 V resistive load
0.5 A DC 30 V inductive load (L/R = 40 ms)
Contact minimum recommended
rating
12 V 100 mA
Contact type Normally open
Default contact condition Closed when power applied and drive OK
Update rate 1 ms
To prevent the risk of a fire hazard in the event of a fault, a
fuse or other over-current protection must be installed in the
relay circuit.