Site Preparation
22
7750 SR ESA 100G Chassis Installation Guide
Release 20.5
3HE 16094 AAAA TQZZA Issue: 01
Protection is typically achieved by deploying the product in a cabinet that is sealed
and is provided either with air-to-air heat exchangers or with air-conditioning and/or
heaters as required for the local climate. If the cabinet is the type that allows outside
air to ventilate the cabinet, it must have Hydrophobic Membrane filters, at the air inlet
and air exit, with all other parts properly sealed against outside contaminants and
moisture. Typically, cabinets that comply with Telcordia GR-487, Generic
Requirements for Electronic Equipment Cabinets, provide this level of protection.
The ambient air temperature must be within the specifications defined in Table 5.
For proper thermal performance, the following conditions must be met:
For seismic applications, the rack must be a Telect Global Seismic Frame (GS
series).
The rail mounting holes in the equipment rack must align with the mounting
holes on the chassis mounting brackets. The 7750 SR ESA 100G mounting
brackets are factory-installed for mounting in a 19-inch rack.
Table 5 Environmental Specifications
Category Specification
Temperature Operating: 41°F to 104°F (5°C to 40°C)
Non-operating: -40°F to 158°F (-40°C to 70°C)
Humidity Operating: 5 to 85% non-condensing
Non-operating: 10% to 95% non-condensing
Altitude 2000 m, 104°F (40°C)
Vibration IEC 68-2-64, IEC 68-2-6
Shock IEC 68-2-27
Drop IEC 68-2-31