NORDAC SK 5xxE Manual
116 Subject to technical alterations BU 0500 GB
Parameter Set value / Description / Note Device Supervisor
Parameter
set
P711 Output status
(SK 520E)
Displays the actual status of the signal relays. 0000 ... 01FF (hex)
Bit 0 = Output 1 (K1)
Bit 1 = Output 2 (K2)
Bit 2 = Output 3 (DOUT1)
Bit 3 = Output 4 (DOUT2)
⎫
⎬ only with SK 52x/53xE
⎭
P712 Voltage analog input 2
0.00 ... 10.00 V Displays the measured analog input value 2.
P714 Operating time
0.10 ... ___ h This parameter shows the time for which the FI was connected to the mains and was ready for
operation.
P715 Enablement time
0.00 ... ___ h This parameter shows the time for which the FI was enabled and supplied current to the output.
P716 Current frequency
-400.0 ... 400.0 Hz Displays the current output frequency.
P717 Current rotation speed
-9999 ... 9999 rpm Displays the actual motor speed calculated by the FI.
P718 ... - 01
... - 02
... - 03
Current set frequency
-400.0 ... 400.0 Hz
Displays the frequency specified by the set point. (see also 8.1 Set point processing)
... - 01 = current set frequency from the setpoint source
... - 02 = actual setpoint frequency after processing in the FI status engine
... - 03 = actual setpoint frequency after the frequency ramp
P719 Actual current
0.0 ... 999.9 A Displays the actual output current.
P720 Current torque current
-999.9 ... 999.9 A Displays the actual calculated torque-developing output current (active current). Basis for
calculation are the motor data P201...P209 ... .
Æ negative values = generator, Æ positive values = drive
P721 Actual field current
-999.9 ... 999.9 A Displays the actual calculated field current (reactive current). Basis for calculation are the motor
data P201...P209 ... .
P722 Actual voltage
0 ... 500 V Displays the actual AC voltage supplied by the FI output.