6 Operation
6.1 Function of the display and operating elements
Drain/Info key
press key shortly: Opens and closes the drain valve (manual drain-
ing).
Note: the drain valve is automatically closed after 10 minutes.
press key for a extended period of time (>3 sec.): activating the
info mode
red LED “Error”
in normal operating mode
The LED lights in case of a malfunction of the unit. Further opera-
tion is no longer possible, the heating voltage is interrupted.
The LED ashes alternately with the green LED if the external
safety chain (ventilation interlock, safety humidistat, etc.) is open.
in info mode
LED ashes in intervals if a malfunction is present. The number of
“ashes” per interval indicates the left digit of the error code.
yellow LED “Warning and info indication”
in normal operating mode
The LED lights if the cylinder maintenance is due (see chapter 7) or
the maintenance indication is not reset after the maintenance (see
chapter 7.6).
in info mode
LED ashes in intervals if a malfunction is present. The number of
“ashes” per interval indicates the right digit of the error code.
green LED “Steam”
in normal operating mode
The LED lights if the unit produces steam.
The LED ashes alternately with the red LED if the external safety
chain (ventilation interlock, safety humidistat, etc.) is open.
in info mode
LED ashes in intervals. The number of “ashes” per interval multiplied
by 10 indicates the current steam output in %.
Unit switch
Switches the unit on and off. The switch is illuminated when the unit is
switched on.