Installation
3-46
Part 1024496_06
2014 Nordson Corporation
Installing Melter Outputs (contd)
Table 3‐9 Output Data
Output Terminals
Operating
Parameter
Control Options Note
Standard Outputs
1 1 and 2 40 0 ‐ Output Disabled
1 ‐ Ready (Default)
2 ‐ Ready and the pump is on
3 ‐ Fault
4 ‐ Tank Low Level
5 ‐ Service LED is On
6 ‐ Alert
A
A
A
B
A
C
2 3 and 4 41
Same as parameter 40 (Default=3)
3 5 and 6 42
Same as parameter 40 (Default=4)
Optional Outputs
4 1 and 2 43
0 (Disabled)
D
5 3 and 4 44
0 (Disabled)
6 5 and 6 45
0 (Disabled)
7 7 and 8 46
0 (Disabled)
NOTE A: When control option condition occurs, contacts close. Contacts are normally open when power is off.
B: When control option condition occurs, contacts open. Contacts are normally open when power is off.
C: Control option 6 provides an output signal when a potential fault is detected. If control option 3 and 6 are both used,
then both a fault output and an alert output signal will be present when the fault LED turns on.
D: For wiring information, refer to the instruction sheet that is provided with the optional I/O expansion card