100 AFP-200 Instruction PN 15511:F2 10/11/99
Appendix G  Pre-Alarm (AWACS) Applications
General
The control panel includes a facility to give early warning of incipient or potential fire conditions (U.S. Patent
Pending). This is a two level Pre-Alarm function called AWACS™ (Advance Warning Addressable Combustion
Sensing). The two levels are Alert and Action.
Alert Level Pre-Alarm Operation
The control panel software, in addition to checking
for alarm levels, will check for Pre-Alarm thresh-
olds for each ionization or photo smoke detector
(not analog thermal detectors). If a level is reached
that exceeds the programmed Alert threshold, the
Alert condition is indicated. As an example, a
typical display is shown to the right.
PREALM is the Pre-Alarm status banner.
ALERT indicates that the Alert level is reached.
50% is the reading of smoke in approximate percent of alarm. This is a real-time display which is updated
every few seconds to show the current reading of this detector. In this case, assume that zone 99 is programmed
to ALERT= 40% OF ALARM. This means Alert will occur at measured smoke levels that exceed .40 x 2.0%
per foot obscuration (low) = 0.80% per foot obscuration. In the example above, the reading is at 50% of alarm,
therefore the control panel is in Alert condition.
2.0% is the programmed alarm threshold (2.0% per foot obscuration is the low sensitivity setting).
The following functions are performed at Alert level:
The above message is sent to the history file and (if they are installed) to the LCD-80 and printer. The message
is sent (and time stamped) only at the time that it first occurred. This historical data could provide valuable
information about the progress of a fire.
The Pre-Alarm LED flashes and the piezo sounder pulses until acknowledged.
Zone 99 is activated. Not activated are Zone 00 (general alarm) or any other zone, or trouble relay or alarm
relay.
The Pre-Alarm indication for this detector will restore automatically to normal if its sensitivity drops below
Alert level. Zone 99 clears automatically when no Pre-Alarm conditions exist.
A subsequent alarm, or an Action level condition for this detector will clear the Alert indication.
PREALM@SMOKE(PHOTO)
WEST@HALLWAY@FLR@5
50%@2.0%@ALERT
12:00P@12/25/97@D13