AFP-2800 - Fire Indicator Panel – Panel Operation Page 45
©
N
OTIFIER
I
NERTIA
P
TY
L
TD
,
2001
WWW
.
INERTIA
.
COM
.
AU
Input modules:
SELECTED POINT : L1M1
L1M1 > BREAK GLASS MAIN FOYER
DEVICE TYPE > FMM-101/MMX-1010 MINI MON
ZONE NO. > 2
ZONE TYPE > MCP
ALARMED? (Y/N) > Y
LATCHED? (Y/N) > Y
TIMED? (Y/N) > N
AVF? (Y/N) > N
FLASHSCAN MENU – PROG
A = 0
F = 0
I = 0
N = 0
01 OCT 1999 14:44:37
BACKSP
ENTER
Actions:
• Press the BACKSP
button to delete an incorrect
character.
• Press the ENTER
button to step through options.
• Press the YES
or NO buttons when highlighted
to answer Y/N options.
• Use external QWERTY keyboard to edit
descriptors and zone type.
• The numerical keyboard can be used for numerical
entries.
• When entering device type a numerical pick list will
appear at the bottom of the screen.
• Refer to appendix for more information on options
and sensitivity settings.
• You will be prompted Yes/No to save changes
when finished.
Output modules:
SELECTED POINT : L1M10
L1M10 > EWIS OUTPUT #1
DEVICE TYPE > FRM-1/CMX-2 RELAY O/P
FLASHSCAN MENU – PROG
A = 0
F = 0
I = 0
N = 0
01 OCT 1999 14:44:37
BACKSP
ENTER
Actions:
• Press the BACKSP
button to delete an incorrect
character.
• Press the ENTER
button to step through options.
• Press the YES
or NO buttons when highlighted
to answer Y/N options.
• Use external QWERTY keyboard to edit
descriptors and zone type.
• The numerical keyboard can be used for numerical
entries.
• When entering device type a numerical pick list will
appear at the bottom of the screen.
• Refer to appendix for more information on options
and sensitivity settings.
• You will be prompted Yes/No to save changes
when finished.
Once the output module name and type has been saved, you will then be transferred to the script entry screen and
be prompted to enter a script for the output. Please refer to page 65 for more information on entering scripts.
www.PDF-Zoo.com