Actual Fault Code Displayed Possible causes
No Response FAULT (F01) The device in fault is not communicating with the LCM. This fault
can occur if the device is not physically connected, damaged or
set at wrong address.
Mismatched
Hardware Type
FAULT (F02) The actual device type is different to the programmed type. This
fault would occur if an incorrect device type is used such as a heat
detector instead of a photo optical detector.
Devices At Same
Address
FAULT (F03) Two devices have the same address on the loop.
Incorrect Response FAULT (F04) The device has returned an incorrect response. This fault can
occur if the device is faulty or the loop wiring is substandard. If the
resistance of the entire loop wire exceeds 50 ohms, this fault will
be observed intermittently.
Open Circuit FAULT (F05) An Analog module does not have the End Of Line resistor
connected or an incorrect value of EOL is used.
Short Circuit FAULT (F06) There is a short circuit on the output terminals of a Analog relay
module.
Low Threshold FAULT (F07) A low threshold fault indicates a faulty detector which needs to be
replaced.
Maintenance Alert FAULT (F08) Analog detector needs cleaning.
Maintenance Urgent FAULT (F09) Analog detector needs cleaning urgently. Once the detector is in
maintenance urgent fault it will no longer provide reliable detection
of fire.
Verify Count Over 20 FAULT (F010) Not used on AFP-2800/2802
Detector Failed Test FAULT (F011) LCM performs a test on each detector every 2 – 3 hours. This
fault can occur if the device is faulty or the loop wiring is
substandard. If the resistance of the entire loop wire exceeds 50
ohms, this fault will be observed intermittently.
Security Tamper FAULT (F012) Not used on AFP-2800/2802
Low Temperature FAULT (F013) Not used on AFP-2800/2802
Ground Fault FAULT (F014) Less than 50kohms resistance to ground. The Ground Fault LED
on the affected LCM will be ON (refer to page 114)
Charger Fault FAULT (F015) Not used on AFP-2800/2802
Battery Low FAULT (F016) Not used on AFP-2800/2802
Battery High FAULT (F017) Not used on AFP-2800/2802
General Trouble FAULT (F018) General fault code that LCM uses when it can not detect the
actual problem with the device. This fault can occur if the device is
faulty or the loop wiring is substandard. If the resistance of the
entire loop wire exceeds 50 ohms, this fault will be observed
intermittently.
Missing Address FAULT (F019) Not used on AFP-2800/2802
AC Fail FAULT (F020) Not used on AFP-2800/2802
Module External
Power Loss
FAULT (F021) 24 volt power is not connected to the Analog module.
(Conventional Zone and Control modules)
Wrong OEM Device
Type
FAULT (F022) The device on the loop is using the wrong communication
protocol. Replace the device with a version that has compatible
protocol with the panel.
RFX Communication
Loss
FAULT (F023) Not used on AFP-2800/2802
Beam Blocked FAULT (F024) Beam Detector Fault - Beam path blocked
Alignment Mode FAULT (F025) Beam Detector Fault - Detector in alignment mode
Device Disabled FAULT (F026) Not used on AFP-2800/2802
Zone Disabled FAULT (F027) Not used on AFP-2800/2802
Initialisation Mode FAULT (F028) Beam Detector Fault - Detector initialising