Compatible Devices
AFP-2800/2802 Manual – P/N 11249 11-Mar-08 13
4.3 COMPATIBLE BATTERIES
In general, any Sealed Lead Acid (SLA) battery, or Wet Lead Acid battery designed for stationary use is
compatible with the AFP2800/2802 Fire Indicator Panel. The use of Nickel Cadmium batteries is not
recommended.
Manufacturer Type Number Voltage Capacity (Ah) Qty Required
Best and Best SLA BP17-12 12 17 2
Best and Best SLA BP24-12 12 24 2
Best and Best SLA BP40-12 12 40 2
Olympic Batteries SLA CJ12-7 12 7 2
Olympic Batteries SLA CJ12-12 12 12 2
Olympic Batteries SLA CJ12-18 12 18 2
Olympic Batteries SLA CJ12-26 12 26 2
Olympic Batteries SLA CJ12-33 12 33 2
Olympic Batteries SLA CJ12-40 12 40 2
Olympic Batteries SLA CJ12-88 12 88 2
Olympic Batteries SLA CJ12-100 12 100 2
NOTES:
Automotive batteries must not be used.
The use of Nickel Cadmium batteries is not recommended.
The batteries could be seriously and permanently damaged if they are permitted to discharge below 20V DC
when placed in series.
The NPS series of power supplies will only charge the battery if the terminal voltage is above 12V when
measured across 2 batteries in series.