Panel Operation
54 AFP-2800/2802 Manual – P/N 11249 11-Mar-08
Once you have selected the input point to trigger the “single push button isolate” you will be asked to enter
“isolate range” of points to be entered as follows.
POINT 1.101.I2 WILL ISOLATE:
POINTS > L1D1 L1D2 L1D3 L1D4;
Enter points or zones to isolate
Seperated by a space, comma or ‘AND’
e.g. 1.2.Z3 1.2.Z4 AND L2D5,L2D6
Use arrows to move arround.
INS,DEL, to edit lines.
ENTER to accept line and/or
Skip to next item
ESC to leave this screen
ISOLATE RANGE
20 JULY 2002 14:44:37
ENTER
Please enter the information below:
A = 0
F = 0
I = 0
N = 1
DAY MODE
Actions:
Use an external QWERTY keyboard to enter in the
points that are to be isolated/de-isolated by the
button press.
Points entered should be separated by spaces or
commas and terminated with a semicolon (;)
Press ENTER once complete.
Zxxx can not be used when entering isolate groups
using the keyboard.
6.3.4.9 SERVICE MENU – ISOLATE – NETWORK
This menu will allow the operator to perform a read status and then isolate zones and points programmed on
remote nodes.