Printing Reports Installed Points Report Screen
56 NFS-3030 Operating P/N 51344:C 11/4/03
the field, then press ACCEPT. The report looks like this.
Panel Circuits: Press to print a report of installed panel circuit points. The report resembles
the installed SLC points with exceptions relative to panel circuits. Refer to the field identification
below.
GENERAL ZONES: Press to print a report of installed general zones.
NORMAL SMOKE (ION) Detector L02D129 *** *** NTL* *** ** 6666
Z002 , , , , , , ,
, , L02D129
Status
Software
Type ID
Detector
or Module
Point label,
extended label
Multi-Detector
Co-op
Addresses
Local Mode Participation (Y or N)
Alarm Tracking (T) or Latching (L)
Prealarm Alert (T) or Action (L)
Alarm Verification Testing (V or *)
Custom
Action
Message
No.
Weekly
Occupancy
Schedule No.
Left to right - Alarm Threshold occupied, Alarm Threshold unoccupied,
Prealarm Threshold occupied, Prealarm Threshold unoccupied
******INSTALLED POINTS**********************************************************
NORMAL SMOKE (ION) Detector L02D129 *** *** NTL* *** ** 6666
Z002,,,,,,,
, , L02D129
ON RELAY Module L02M005 NL * *** **
ZL001,,,,,,,
, , L02M005
********************************************************************************
Device
Address
Ten zone fields of zone map (separated by commas)
Field Identification
SLC Detector Installed Points
******INSTALLED POINTS**********************************************************
NORMAL RELAY Panel Circuit P1.5 NL * 005 **AWSI
ZL000 , , , , , , ,
, , P01.5
OFF MONITOR Panel Circuit P2.2 NT * *** ******
ZL30 , , , , , , ,
, , P02.2
********************************************************************************
Status
Software
Type ID
Point label,
extended label
Local Mode Participation (Y or N)
Alarm Tracking (T) or Latching (L)
Alarm Verification Testing (V or *)
Custom
Action
Message
No.
Weekly
Occupancy
Schedule
No.
Device Address
Ten zone fields of zone map (separated by commas)
Field Identification
SLC and Panel Circuit Module Installed Points
Silenceable (S or *)
Walk Test Participation (W or *)
Switch Inhibit (I or *)
Audible Walk Test (A or *)
******INSTALLED POINTS**********************************************************
ON GENERAL ZONE General Alarm Z000
ON GENERAL ZONE Zone 001 Z001
OFF GENERAL ZONE Zone 002 Z002
********************************************************************************