NFS2-640/E Installation Manual — P/N 52741:P2 7/10/14 11
Section 2: System Overview
2.1 System Description
The NFS2-640/E control panel is a modular, intelligent fire alarm control panel (FACP) with an
extensive list of powerful features. The control panel uses the CPS-24/E integral power supply with
battery charger. This is combined with a mounting chassis and cabinet to create a complete fire
alarm control system. The panel supports FlashScan® protocol and has network capabilities. A
single SLC loop is supported with the basic equipment package; a second SLC loop can be added
by attaching an optional loop expander module (LEM-320).
Modular devices mount to the chassis to provide additional output circuits, including voice and
telephone modules to form a complete voice evacuation system. Five cabinet options are available
for enclosing system components; each is available in red or black.
The control panel has the capacity for installing up to 636 addressable points; 159 detectors and
159 monitor/control modules per SLC (Signaling Line Circuit).
2.1.1 Standard Features
Uses Notifiers VIEW® early warning fire detection and the FlashScan or Classic Loop
Interface Protocol (CLIP) families of detectors and modules
Integral power supply with battery charger
Four standard Notification Appliance Circuits (NAC), Class A or B
Alarm, Trouble, Supervisory and Security relays
Support for 32 annunciator addresses, with 10 special annunciator groups
Supports Style 4, Style 6, Style 7 SLC loops
Connections to easily mount an expander board to add a second SLC loop
Releasing service using on-board NACs or FCM-1 modules
Logic Equations
Display scroll selection
Alarm verification supervisory indication (NYC)
Supervisory duct detectors
Supports Advanced Warning Addressable Combustion Sensing (AWACS) algorithms
Network operation
Battery charger supports 18 to 200 amp hour sealed lead-acid batteries
EIA-485 connections for wiring ACS annunciators (including LDM custom graphic
annunciators), TM-4 transmitter
EIA-232 connections for printer, CRT, printer/CRT, or network operation
Autoprogram feature for faster programming of new devices
The control panel provides 6 amps of usable output power in an alarm condition; it provides
3 amps of usable output power in normal or continuous operating conditions
Diagnostic LEDs and switches
Ground fault detection (0 ohm impedance)
Battery and battery-charger supervision, voltage-monitoring, and current-monitoring
Disconnect of deeply-discharged battery (low battery disconnect)
Programmable for strobe synchronization
Mass Notification System compatible