21
ML0044B December 1, 2017 Copyright 2016 Bitronics, LLC
1.4.2 Outputs
4 outputs, 3 Normally Open (NO), 1 isolated, can be wired for Normally Closed (NC) or
Normally Open (NO) operation for energized or de-energized condition. Output
terminals have internal 510V clamp. Channels 1-3 share a common return, however,
channel 4 has an independent return. One additional channel is for alarming. The
recommended torque ratings for the terminal block wire fasteners are listed in the
Physical Specifications table (section 1.3).
Output Maximum Switched Current (Resistive)
Voltage
Tripping
(C37.90
Resistive)
Continuous
Carry
Break
(Inductive)
24Vdc 30A 5A 8A
48Vdc 30A 5A 700mA
125Vdc 30A 5A 200mA
250Vdc 30A 5A 100mA
Output Operate Time (does not include protocol delays)
Assert (Close time "N.O."): 8ms
Release (Open time "N.O."): 3ms
Isolation
I/O Terminals to Case: 2000Vac, 1min
Input Channels 1-4 to Input Channels 5-8: 2000Vac, 1min
Input Channels 1-4 to Output Channels 1-4: 2000Vac, 1min
Output Channel 4 to other Output Channels: 2000Vac, 1min
Refer to figures 1 and 2 below for simplified circuitry and terminal wiring assignments.