Adesys bv, Wateringen, NL
Installation instructions
Octalarm-T2 / T4 / T8 / T16
29
The Octalarm only needs the A and B connections to the telephone network to function properly.
When not active, A and B are put through to A’ and B’, respectively. The most common type of
connection is:
overige
rand-
apparatuur
overige
rand-
apparatuur

If the Octalarm is connected to a fully wired RJ-11 main connection by the telephone company,
without a connecting plug, it may cause a short-circuit in the telephone network, owing to the A-A’
and B-B’ reconnection when not active. If so, set up an additional RJ-11 connection box with only
the two centre pins connected, or else use a 2-core connection cable rather than the standard 4-
core model supplied.

Avoid connecting the Octalarm behind a telephone switchboard. In the case of a network failure,
the connections of telephone switchboards often stop working. This will prevent the Octalarm from
sending a telephone alarm!
If the Octalarm has to be connected together with a telephone switchboard, do so according to the
following diagram:
overige
rand-
apparatuur
overige
rand-
apparatuur
PABX
(interne
centrale)