Installation instructions
Adesys bv, Wateringen, NL
46 Octalarm-T2 / T4 / T8 / T16
DELAY TIME: 01 MIN
Here you can enter the desired delay time (from 1 to 99 min).
In case of a switched on alarm buzzer, the following question is asked:
ALARM BUZZER OFF: AFTER TEL. RESET / BY RESET KEY / AFTER DELAY
Set the stop condition for the alarm buzzer:
•
AFTER TEL. RESET the alarm buzzer is switched off after a successful telephone report.
The buzzer keeps sounding after 15 failed report attempts. If the telephone dialler key is
switched off, the alarm buzzer will sound until the reset key is pressed.
•
BY RESET KEY
the alarm buzzer only stops after pressing the reset key.
• AFTER DELAY
the alarm buzzer stops automatically after the set delay time has elapsed.
With this option, the following additional question appears:
DELAY TIME: 01 MIN
Set the desired delay time here (from 1 to 99 min).
VOLUME INTERNAL BUZZER: 2
Select the desired volume for the built-in buzzer. The Octalarm allows you to hear the
chosen volume during programming.
NIGHT TO DAY: ALARM BUZZER ON / ALARM BUZZER OFF
Here you can define whether the buzzer key has to be switched on or off when the night time
mode is disabled.
DIALLER NIGHT: OFF / ON
Define whether a telephone report at night is desirable. If so, the following question appears:
DIALLER DELAY: 00 MIN.
Here you can enter the desired delay time (from 1 to 99 min).
NIGHT TO DAY: DIALLER ON / DIALLER OFF
Here you can define here whether the telephone dialler key has to be switched on or off
when the night time mode is disabled.
KEYBOARD INHIBIT AT NIGHT: NO / YES
In case yes is chosen, all keys on the operation panel will be locked, irrespective of the
keyboard access being protected with an access code or not.
18.12 Prog 95 “sensor test”
This program enables the one- by- one testing of the Sensornet terminal blocks. If the Octalarm
recognizes the sensor, this will be reproduced on the display.
Take care to ensure that the Octalarm always "sees" only one sensor connected at the same time,
otherwise the message SENSOR DEFECTIVE appears. If necessary, disconnect Sensornet from the
Sensornet input and connect the block to test it directly to the input.