Installation instructions
Adesys bv, Wateringen, NL
42 Octalarm-T2 / T4 / T8 / T16
Changes of the dialling order are to be handled carefully, because in case of a wrong set-up, it is
possible that an alarm will no longer be reported! Therefore, always check if the numbers entered
(A-J) at the dialling order that have actually been entered are a call number (see: part 7 “SET ”).
In case more than one reporting group is set and no reset is given by the first reporting group, it
can take a long time (the time needed to carry out 15 reports, plus the delay times set with them)
before the second reporting group will be called.
Changes of the dialling order can lead to an alteration of the order in which simultaneously
occurring alarms are reported. See for the regarding effects: paragraph 4.5 “More than one alarm
simultaneously”.
AUTOMATIC REPEAT: YES / NO
Define whether an automatic repeat of a telephone alarm is desired.
•
NO the telephone report will be carried out only once, following the dialling order set with
the reporting channel.
• YES
the telephone report will be started again according to the dialling order set with the
alarm channel after a waiting time, irrespective of a former reset by telephone. The
repeating report will cease only if the alarm expires (alarm indicator off) or when the
relevant selection key on the Octalarm is switched off. The automatic repeating will be
finished after 24 hours.
AUT. REPEAT AFTER: 01:00 (HRS:MIN)
Set the waiting time for repeating telephone alarm here.