PLATINUM
TM
Series User’s Guide
54
Reference Section: Operating Mode (oPER)
Return to RUN Mode or to displaying “RUN depending on the Operating Safety parameter
setting (4.5.2 Operating Mode Confirmation (INIt > SFty > oPER)).
6.6 Stop Process (oPER > StoP)
Select the Stop Operating Mode (StoP) to turn off all control outputs. The current process
value remains with flashing digits in this mode. Alarm conditions are maintained.
Return to RUN Mode or to displaying “RUN depending on the Operating Safety parameter
setting (4.5.2 Operating Mode Confirmation (INIt > SFty > oPER)).
6.7 Clear Latched Alarms (oPER > L.RSt)
Select the Clear Latched Alarms command (L.RSt) to clear currently latched Alarms.
Alternatively, use digital input to activate the L.RSt command if configured in the PRoG menu
as explained in
5.3.4 Alarm Latching (PRoG > ALM.1, ALM.2 > LtCH).
Return to RUN Mode or to displaying “RUN depending on the Operating Safety parameter
setting (4.5.2 Operating Mode Confirmation (INIt > SFty > oPER)).
6.8 Display Valley Reading (oPER > VALy)
Select Display Valley Reading (VALy) to change the process value displayed to the lowest
reading since VALy was last cleared.
Clear the VALy reading buffer. Return to RUN Mode or to displaying “RUN” depending on the
Operating Safety parameter setting (4.5.2 Operating Mode Confirmation (INIt > SFty > oPER)).
Note: Using the other buttons to navigate away from VALy does not clear the VALy reading
buffer.
6.9 Display Peak Reading (oPER > PEAk)
Select Display Peak Reading (PEAk) to change the process value displayed to the highest
reading since PEAk was last cleared.
Clear the PEAk reading buffer. Return to RUN Mode or to displaying “RUN” depending on the
Operating Safety parameter setting (4.5.2 Operating Mode Confirmation (INIt > SFty > oPER)).
Note: Using the other buttons to navigate away from PEAk does not clear the PEAk reading
buffer.
6.10 Standby Mode (oPER > Stby)
Select Standby Mode (Stby) to disable outputs and Alarm conditions. Stby is displayed until
navigating elsewhere. Navigate to any desired initialization or programming settings to
change them or to adjust the process.
Return to RUN Mode or to displaying “RUN depending on the Operating Safety parameter
setting (4.5.2 Operating Mode Confirmation (INIt > SFty > oPER)).
Omega Engineering | www.omega.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omega CN16Pt and is the answer not in the manual?

Omega CN16Pt Specifications

General IconGeneral
BrandOmega
ModelCN16Pt
CategoryController
LanguageEnglish

Related product manuals