9.2.24 ANALOG OUTPUT CALIBRATION NUMBERS
The analog output calibration numbers (see Figure 12-1) are printed on the
optional analog output board. These four numbers (CAL VZ, CAL VS,
CAL mAS), must be entered into the meter to ensure that the analog output
board is calibrated with the microprocessor.
MENU MIN/MAX/MENU *
BUTTON BUTTON
MAIN MENU SUB MENU DESCRIPTION
“CAL VZ” 0 to 59999 Calibration number marked on the
analog output board must be entered
for voltage zero.
“CAL VS” 0 to 59999 Calibration number marked on the
analog output board must be entered
for voltage span.
“CAL mAZ” 0 to 59999 Calibration number marked on the
analog output board must be entered
for current zero.
“CAL mAs” 0 to 59999 Calibration number marked on the
analog output board must be entered
for current span.
NOTE: After you complete your programming you may want to go back and
remove the jumper in S3A position on the main board to insure against any
unauthorized changes.
Once you are done with the changes, press the ‘MENU’ button to display.
The meter advances to run mode showing the currently measured values.