EasyManua.ls Logo

Omega DP41-S - Page 88

Omega DP41-S
175 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8-44
STRAIN
0
8
Scaling to
Display
Engineering
Units
Pressing the ‘MENU’ button will take you through all the different
menu’s listed below. When you wish to enter a menu, to the
submenu 1 stage, press the ‘MIN’ button. To make a selection, in
submenu 1, press the ‘MAX’ button. If the submenu has more
than one item to select use the ‘MIN’ button to scroll to the next
item of choice and again use the ‘MAX’ button to make your
selection.
After making all of your choices, in submenu 1, enter these selec-
tions by pressing the ‘MENU’ button which will momentarily flash
“STORED” on the display.
If the item selected in submenu 1 has a submenu 2 associated with
it, press the ‘MIN’ button to enter the submenu 2. Select your
choice by pressing the ‘MAX’ button and enter your choice with
the ‘MENU’ button. Pressing the ‘RESET’ button one time brings
you back one menu item, pressing the ‘RESET’ button two times
returns you to the run mode.
WARNING! this also results in a hard reset of peak and valley and
your setpoints.
Proceed through the flow chart below entering the values listed in
submenu 1 and 2 columns.
MENU SUBMENU 1 SUBMENU 2 DESCRIPTION
L1CNF Skip past
L2CNF Skip past
L3CNF Skip past
L4CNF Skip past
INPUT BRIDGE Meter’s input.
RDG.CNF RDG.1=0 Scaling y=mx+b
RDG.2=0 Active decimal point
RDG.3=0 Normal display brightness
RDG.4=1 Leading zeros suppressed
RDG.5= Disregard not used
RDG.6= Disregard not used
RDG.7=0 External hard reset vs
only peak reset
continued next page