21
Diagnostic of Rotating Machines Insulation
6 Diagnostic of Rotating Machines
Insulation
For motors and generators, the expected life of a stator winding depends on the
ability of the electrical insulation to prevent winding faults. High temperatures,
and high rates of temperature changes, can generate inner micro-voids
particularly at the interface between Mica and resin, and between
semiconductive layers and the resin. Partial discharges in these voids can cause
a growing of the voids by erosion and complete breakdowns are only a matter
of time.
6.1 Tan Delta Measurements
Capacitance (C) and Dissipation Factor (DF) - often also called "Tan delta" or
power factor (PF) - measurement is an established and important insulation
diagnosis method. It can detect:
insulation failures
aging of insulation
contamination of insulation liquids with particles
water in solid and liquid insulation
partial discharges, e.g., in voids and cracks.
Definition
In an ideal capacitor without any dielectric losses, the insulation current is
exactly 90 ° leading according to the applied voltage. For a real insulation with
dielectric losses this angle is less than 90 °. The angle
δ = 90 °- ϕ is called loss
angle. In a simplified diagram of the insulation, C
p
represents the loss-free
capacitance and R
p
the losses (figure 6-1). The definition of the dissipation
factor and the vector diagram are shown in figure 6-2.