9
Safety Instructions
2.3 Operating the CP CR500
For safe CP CR500 operation:
1. Make sure that only the green light "0" on the CPC 100's front panel is lit.
CP TD1 may not give any acoustic warning sound.
2. Secure the CP CR500 unit with a chain or a barrier tape at a distance of at
least 1 m / 3 ft to prevent an accidental entering of the dangerous zone
during operation.
3. Connect CP CR500, CPC 100 and CP TD1 as described in this user manual.
4. Do not operate the CP CR500 without connecting the safety circuit!
5. Make sure that the connectors are tighlty fit before turning on the high
voltage.
6. Turn on the high voltage only for the short time that the measurement
requires.
7. Do not touch cables while operating.
8. Do not leave the test set during operation.
9. Once the measurement is finished, press the emergency stop button on the
CPC 100's front panel.
10.After you have finished working with the CP CR500, turn the safety key on
the CPC 100's front panel to "lock" (vertical) and remove the key to avoid
anyone turning on the high voltage accidentally.