SECTION G
Tuning
In VF mode the Omron inverter is manually tuned to give the desired performance from the
inverter. The parameters to set are: -
E 1-04 Maximum Frequency 50Hz
E 1-05 Maximum Voltage 415V
E 1-06 Base Frequency As motor data plate
E 1-13 Base Voltage As motor data plate
E 2-01 Motor Rated FLA As motor data plate
E 2-02 Motor Rated Slip ((Rated RPM—Nameplate RPM)/Rated RPM)*50 in Hz
E 2-03 No Load Current Measure empty car up current and set 1 Amp higher
E 2-05 Term Resistance Set to 75% of measured resistance between two of the motor
phases