Using Digital Operator
10
Example of Parameter Settings
The following example shows how to set 2 to enable the frequency reference control terminal for 0- to 10-V input in parameter n03
(Frequency Reference Selection).
Cancels set
data.
In approximately 1 s.
Complete
Enable the frequency reference
control terminal for 0- to 10-V input.
Key sequence Indicator Display example Explanation
Power ON
Press the Mode Key repeatedly until the PRGM indicator is
lit.
Use the Increment or Decrement Key to set the parameter
number.
Press the Enter Key.
The data of the selected parameter number will be displayed.
Use the Increment or Decrement Key to set the data. At that
time the display will flash.
Press the Enter Key so that the set value will be entered and
the data display will be lit. (see note 1)
In approximately 1 s. The parameter number will be displayed.
Note: 1. To cancel the set value, press the Mode Key instead. The parameter number will be displayed.
2. There are parameters that cannot be changed while the Inverter is in operation. Refer to the list of parameters. When at-
tempting to change such parameters, the data display will not change by pressing the Increment or Decrement Key.