8-21
8 Using Expansion Units and Expansion I/O Units
CP1E CPU Unit Hardware User’s Manual(W479)
8-2 Analog Output Units
8
8-2-4 Flow of Operation
(6) Program Example (CP1W-DA041)
Analog output Output range Range code Set data Destination word
Output 1 0 to 10 V 001 1001 (9 hex) Wd n+1
Output 2 4 to 20 mA 100 1100 (C hex) Wd n+1
Output 3 -10 to 10 V 000 1000 (8 hex) Wd n+2
Output 4 Not used. −(000) 0000 (0 hex) Wd n+2
P_On
T5
T5
T5
MOV
#80C9
102
TIM5
#0002
D200
102
MOV
D202
104
MOV
MOV
#8008
103
D201
103
MOV
Always ON Flag
Execution
condition
Execution
condition
Execution
condition
First Cycle Flag
A200.11
Writes set data C and 9.
Writes set data 0 and 8.
Writes analog output 1 conversion data.
Writes analog output 2 conversion data.
Writes analog output 3 conversion data.