Transistor Outputs (Sinking or Sourcing)
Item
Specification
20CDT-D
20CDT1-D
30CDT-D
30CDT1-D
40CDT-D
40CDT1-D
60CDT-D
60CDT1-D
8ET
8ET1
20EDT
20EDT1
Max.
switching
capacity
OUT01000 and OUT01001: 4.5 to 30 VDC, 0.2 A/output (See note 1.)
OUT01002 and up: 4.5 to 30 VDC, 0.3 A/output
24 VDC
+10%
/
–5%
,
0.3 A/output
capac
it
y
0.8 A/common
1.6 A/Unit
(See note 2.)
0.8 A/common
2.4 A/Unit
(See note 2.)
0.8 A/common
3.2 A/Unit
(See note 2.)
0.8 A/common
4.8 A/Unit
(See note 2.)
0.9 A/common
1.8 A/Unit
(See note 2.)
0.9 A/common
1.8 A/Unit
Leakage
current
0.1 mA max.
Residual
voltage
1.5 V max.
ON
delay
OUT01000 and OUT01001: 20 µs max.
OUT01002 and up: 0.1 ms max.
0.1 ms max.
OFF
delay
OUT01000 and OUT01001: 40 µs max. for 4.5 to 26.4 V, 10 to 100 mA
0.1 ms max. for 4.5 to 30 V, 10 to 200 mA
OUT01002 and up: 1 ms max.
1 ms max.
(24 VDC
+10%
/
–5%
,
5 to 300 mA)
Fuse 1 fuse/output (cannot be replaced by user) 1 fuse/common
(cannot be
replaced by user)
Circuit
configura
tion
Output LED
Internal
circuits
Sinking Outputs
COM (–)
Sourcing Outputs
OUT
OUT
24 VDC/4.5 to 30 VDC
Output LED
Internal
circuits
COM (+)
OUT
OUT
24 VDC/4.5 to 30 VDC
Note 1. When using OUT01000 or OUT01001 as a pulse output, connect a dummy
resistor as required to bring the load current between 0.01 and 0.1 A. If the
load current is below 0.1 A, the ON-to-OFF response time will be longer and
high-speed pulses (source-type transistor outputs) will not be output. If the
load current is above 0.1 A, the transistor will generate more heat and com-
ponents may be damaged.
2. The total for OUT01000 to OUT 01003 must be 0.8 A maximum. If the ambi-
ent temperature is maintained below 50 °C, however, up to 0.9 A/common
can be used.
Caution Do not apply voltage in excess of the maximum switching capacity to an output
terminal. It may result in damage to the product or fire.
Specifications Section 2-1