354
Handling Errors and Alarms Section 7-10
ERC Indicator and RUN Indicator: Lit, ADJ Indicator: Flashing
This alarm will occur in the case of incorrect operation while in the adjustment
mode. In adjustment mode, the Adjustment Mode ON Flag will turn ON in bit
15 of CIO word n+9.
Note When a PLC error occurs in the adjustment mode, Unit operations will stop
operating. (The input and output values immediately prior to the error will be
held.)
ERC Indicator: Lit, RUN Indicator: Not Lit
The ERC indicator will be lit when the initial settings for the Analog I/O Unit
are not set correctly. The alarm flags for the following errors will turn ON in
CIO word n+9. These alarm flags will turn OFF when the error is cleared and
RUN
ERC
ERH
ADJ
: Lit
: Flashing
: Not lit
Word n + 9 Alarm flag Error contents I/O status Countermeasure
Bit 12 (Adjustment 
mode)
Input Value 
Adjustment 
Range 
Exceeded
In adjustment mode, offset or 
gain cannot be adjusted 
because input value is out of the 
permissible range for adjust-
ment.
Conversion data 
corresponding 
to the input sig-
nal is monitored 
in word n+8. 
If making the adjustment by 
means of a connected input 
device, first adjust the input 
device before adjusting the Ana-
log I/O Unit.
Bit 13 (Adjustment 
mode)
I/O Number Set-
ting Error
In adjustment mode, adjust-
ment cannot be performed 
because the specified input or 
output number is not set for use 
or because the wrong input or 
output number is specified.
Holds the values 
immediately 
prior to the error. 
No data is 
changed.
Check whether the word n input 
or output number to be adjusted 
is set from 11 to 14, or 21 to 24.
Check whether the input or out-
put number to be adjusted is set 
for use by means of the DM set-
ting.
Bit 15 only ON (Adjustment 
Mode)
PLC Error
The PLC is in either MONITOR 
or RUN mode while the Analog 
I/O Unit is operating in adjust-
ment mode.
Holds the values 
immediately 
prior to the error. 
No data is 
changed.
Change the setting in bits 00 to 
07 of D(m+18) and then either 
turn the power supply to the 
PLC OFF and ON or turn ON 
the Special I/O Unit Restart Bit.
RUN
ERC
ERH
: Lit
: Not li