72
Handling Errors and Alarms Section 2-8
ERC Indicator and RUN Indicator: Lit, ADJ Indicator: Flashing
This alarm will occur in the case of incorrect operation while in the adjustment
mode. In adjustment mode, the Adjustment Mode ON Flag will turn ON in bit
15 of CIO word n+9.
n = CIO 2000 + unit number x 10
Note 1. When a PLC error occurs in the adjustment mode, the Unit will stop oper-
ating. (The input values immediately prior to the error are held.)
2. These alarms are output in CIO word n+9 for CS1W-AD041-V1 and
CS1W-AD081-V1, and in CIO word n+19 for CS1W-AD161.
3. These alarms are output in CIO word n+8 for CS1W-AD041-V1 and
CS1W-AD081-V1, and in CIO word n+18 for CS1W-AD161.
4. The operation mode is set in DM word m+18 for CS1W-AD041-V1 and
CS1W-AD081-V1, and in DM word m+19 for CS1W-AD161.
5. Bit 15 is always ON in adjustment mode. When the PLC is in RUN mode
or MONITOR mode, the ERC indicator will be lit.
ERC Indicator: Lit, RUN Indicator: Not Lit
The ERC indicator will be lit when the initial settings for the Analog Input Unit
are not set correctly. The alarm flags for the following errors will turn ON in
RUN
ERC
ERH
ADJ
: Lit
: Flashing
: Not lit
Word n+9/n+19 
(See note 2.) 
Alarm flag Error contents Input status Countermeasure
Bit 12 (Adjustment 
mode)
Input Value 
Adjustment 
Range 
Exceeded
In adjustment mode, offset or 
gain cannot be adjusted 
because input value is out of the 
permissible range for adjust-
ment.
Conversion data 
corresponding 
to the input sig-
nal is monitored 
in word n+8/
n+18 (see note 
3).
If making the adjustment by 
means of a connected input 
device, first adjust the input 
device before adjusting the Ana-
log Input Unit.
Bit 13 (Adjustment 
mode)
Input Number 
Setting Error
In adjustment mode, adjust-
ment cannot be performed 
because the specified input 
number is not set for use or 
because the wrong input num-
ber is specified.
Holds the values 
immediately 
prior to the error. 
No data is 
changed.
• Check whether the word n 
input number to be adjusted is 
set within the following ranges: 
CS1W-AD041-V1: 21 to 24
CS1W-AD801-V1: 21 to 28
CS1W-AD161: 201 to 216
• Check whether the input num-
ber to be adjusted is set for 
use by means of the DM set-
ting (DM word m set to 1).
Bit 15 only ON 
(See note 5.)
(Adjustment 
Mode)
PLC Error
The PLC is in either MONITOR 
or RUN mode while the Analog 
Input Unit is operating in adjust-
ment mode.
Holds the values 
immediately 
prior to the error. 
No data is 
changed.
Set the Unit to normal mode 
either by removing the Unit and 
setting the DIP switch on the 
rear panel or by setting the 
mode in DM word m+18 (see 
note 4), and then restart the 
Unit.
RUN
ERC
ERH
: Lit
: Not lit