Handling Errors and Alarms Section 2-8
Value Does Not Change as Intended
Conversion Values are Inconsistent
Probable cause Countermeasure Page
The input device’s signal range 
does not match the input signal 
range for the relevant input number 
at the Analog Input Unit.
Check the specifications of the 
input device, and match the settings 
for the input signal ranges.
14
The offset and gain are not 
adjusted.
Adjust the offset and gain. 60
When using the 4 mA to 20 mA 
range, the voltage/current switch is 
not turned ON.
Turn ON the voltage/current switch. 31
Probable cause Countermeasure Page
The input signals are being affected 
by external noise.
Change the shielded cable connec-
tion to the Unit’s COM terminal.
36
Insert a 0.01-µF to 0.1-µF ceramic 
capacitor or film capacitor between 
the input’s (+) and (–) terminals.
---
Try increasing the number of mean 
value processing buffers.
55